Link to SXP Vokes home page
Liquid Filtration Symbol: Droplet
Innovation in Filtration

Stream-Line: Insulating Fluid Treatment Systems

Insulating Fluid is vitally important for the safe and efficient operation of many types of electrical equipment. In addition to its insulating properties, the fluid is used as a coolant in transformers and as a means of arc suppression in circuit breakers. In each case the operation of the electrical equipment depends on the purity of the insulating fluid, which in services can be contaminated by particles, water, gases and chemical products.

Power Station Stream-Line at sub station Transformer Euro Tunnel's Le Shuttle

Should electrical equipment be continuously operated with contaminated fluid, it's efficiency will be impaired, resulting eventually in the risk of total failure. Typically insulating fluid is contaminated in the following ways:

  • Particles including fibres, rust and colloidal carbon.
  • Free and dissolved water.
  • Gases produced by fluid ageing, equipment failure and arc suppression in switchgear.
  • Chemical products caused by oxidation, as well as cross contamination by other products.


Although individually each contaminant reduces the insulating characteristics of the fluid by around 20%, the combination of fibres from insulating material and water can reduce its performance by up to 90%.

Insulating fluid treatment maintains the integrity of the fluid and hence the efficient utilisation of the electrical equipment.


Vokes Stream-Line SL20 Vokes Stream-Line SL Range
The Vokes Stream-Line SL range relies on a high efficiency (99.9% at 1µm absolute) 'edge type' filter pack, which can be easily backflushed clean using compressed air.

Utilising a high performance vacuum pump, typically the SL range will, in a single pass, reduce water contamination from 50ppm to 5ppm and dissolved gases from 10% to 0.25% by volume.

The Vokes Stream-Line SL range offers a high efficiency, low maintenance, comprehensive solution for treating insulating fluid.

Available Documents
Acrobat Version
Stream-Line General Brochure
SL05 Operating Instructions
SL10 Operating Instructions
SL20 Operating Instructions
SL40 Operating Instructions
SL60 Operating Instructions
Model Rated Capacity (l/hr)

Mobility

Available Acrobat Documents
Datasheet GA Drawing
SL05 500 Fixed 5053-GA
SL05 500 Mobile 5051-GA
SL10 1000 Fixed 5056-GA
SL10 1000 Mobile 5054-GA
SL20 2000 Fixed 5059-GA
SL20 2000 Mobile 5057-GA
SL40 4000 Fixed 5062-GA
SL40 4000 Mobile 5060-GA
SL60 6000 Fixed 5068-GA
SL60 6000 Mobile 5066-GA

Vokes Stream-Line C6000 Vokes Stream-Line C Range
The Vokes Stream-Line C Range utilises a high efficiency (98.7%@1µm) disposable Vokes Microfine filter cartridge, which has been specially developed for use with insulating fluids.

The C Range of plants are up to 30% more energy efficient than there SL equivalents, and still returns performance synonymous with the Stream-Line name - water contamination reduction from 50ppm to 5ppm, dissolved gases from 10% to 0.25% by volume all in a single pass.

The Vokes Stream-Line C Range offers a compact, high efficiency, low maintenance, comprehensive solution for treating insulating fluid.

Available Documents
Acrobat Version
Stream-Line General Brochure
C1000 Operating Instructions
C2000 Operating Instructions
C4000 Operating Instructions
C6000 Operating Instructions
C12000 Operating Instructions
Model Rated Capacity (l/hr)

Mobility

Available Acrobat Documents
Datasheet GA Drawing
C1000 1000 Fixed
C1000 1000 Mobile
C2000 2000 Fixed
C2000 2000 Mobile
C4000 4000 Fixed
C4000 4000 Mobile
C6000 6000 Fixed
C6000 6000 Mobile 5044-GA
C12000 12000 Fixed 5050-GA
C12000 12000 Mobile

Vokes Stream-Line  FE4 DeAcid Module Vokes Stream-Line De-Acid Modules
In use, insulating oil will with time turn acidic and if not corrected result in the precipitation of sludge leading to, insulation breakdown brought about by restriction of the cooling effect and corrosion of the metal surfaces above the oil level caused by condensed acidic vapours.

Users of electrical equipment utilising insulating oil, should monitor this and other contaminants. Once acidity is detected as having reached a maximum acceptable level, normally between 0.1and 0.5mgKOH/gr, the insulating oil must be either discarded or regenerated.

Vokes Stream-Line Fullers Earth Modules have been developed to be utilised in conjunction with Vokes
Stream-Line SL and C Range plants enabling operators to regenerate their own oil.


 

Vokes Stream-Line STC - Tap Changer Filter Modules
Maintaining the quality of the insulating fluid within a tap changer prolongs the life of the electrical contacts and extends the service interval between insulating fluid changes. Stream-Line STC modules have been specifically developed to satisfy these requirements.

  • Full flexability - programmable controller for operating time and functional period
  • High efficiency filtration (0.5µm nominal)
  • Water absorbent cartridge option available
  • Four standard electrical configurations (415v3ph50Hz, 380v3ph50Hz, 380v3ph60Hz and 440v3ph60Hz)
  • Two flow rates (3l/min and 5l/min)
  • Single enclosure - totally weather protected to IP65
  • Plinth mounted for simple on site locating
  • Easy filter maintenance - element can be changed without shutting down system
Available Documents
Acrobat Version
Stream-Line STC Brochure
Model Rated Capacity (l/hr)

Standard Connection

Available Acrobat Documents
Datasheet Maintenance
STC01 3 ½" BSP
STC02 5 ½" BSP
 
PRODUCTS
Liquid Filtration
Insulating Fluid Treatment
 

Stream-Line SL Range
Stream-Line C Range
Stream-Line De-Acid Modules
Stream-Line STC

Link to SPX Dehydration & Process Filtration